This is a sample report. It is the complete document you receive when you unlock a report — same template, same engine, on one fixed example building. Your own structure gets its own computation, with your inputs and your figures throughout.
Assess your structure — free → See pricing

Lightning Protection Risk Assessment

Content generated 2026-07-01 09:30 UTC · this copy printed 2026-09-19 02:43 UTC
Engine lightning-0.18.0-iec2024 · schema v2
StructureRetail block — 3 storeys (sample) Basis of calculationIEC 62305-2:2024 (Ed. 3.0)
Enginelightning-0.18.0-iec2024 Schemav2
Governing zone risk
7.39e-05
Tolerable
1e-05
Verdict
Exceeds tolerable
Assumptions for missing inputs — the engine filled in the following defaults; verify each before relying on this assessment:
Methodology notes (Ed. 3.0:2024)
A_D = 4 810 m² (3H = 24 m) 30 × 20 m 30 × 20 m
A_D = 4 810 m² (3H = 24 m) 30 × 20 m A_D (§A.2.1.2, eq. A.3) is the ground area a flash can be attracted from: the footprint offset by 3H = 24 m, corners radiused to match. A_M (§A.3, eq. A.8) is the band out to r_M = 350/U_W = 233 m, within which a flash to ground can still damage internal systems. At 194 376 m² it is too large to draw beside the structure at a readable scale, so it is stated rather than shown. To scale, uniform on both axes.

Risk zones

Risk is assessed for each risk zone and compared with the tolerable risk in that zone; protection is required unless every zone complies.

10⁻⁸ 10⁻⁷ 10⁻⁶ 10⁻⁵ 10⁻⁴ R_T Sales floor: R = 3.7e-05 /yr — Exceeds Sales floor 3.7e-05 · Exceeds Storeroom: R = 7.39e-05 /yr — Exceeds Storeroom 7.39e-05 · Exceeds
ZoneRisk RRL1 (injury)RL2 (damage)Tolerable RTVerdict
Sales floor 3.7e-05 9.76e-06 2.72e-05 1e-05 Exceeds
Storeroom 7.39e-05 1.76e-06 7.21e-05 1e-05 Exceeds

Risk component breakdown — governing zone

R_B2 = 4.81e-05 /yr — Fire or explosion — physical damage (S1) R_B2 4.81e-05 R_V2 = 2.4e-05 /yr — Fire or explosion via a connected line — physical damage (S3) R_V2 2.4e-05 R_B1 = 1.1e-06 /yr — Fire or explosion — injury to persons (S1) R_B1 1.1e-06 R_V1 = 5.48e-07 /yr — Fire or explosion via a connected line — injury to persons (S3) R_V1 5.48e-07 R_AT = 8.78e-08 /yr — Touch and step voltages — flash to the structure (S1) R_AT 8.78e-08 R_U = 2.19e-08 /yr — Touch voltage via a connected line — injury to persons (S3) R_U 2.19e-08
ComponentValueDescription
R_AT8.78e-08Touch and step voltages — flash to the structure (S1)
R_B11.1e-06Fire or explosion — injury to persons (S1)
R_B24.81e-05Fire or explosion — physical damage (S1)
R_U2.19e-08Touch voltage via a connected line — injury to persons (S3)
R_V15.48e-07Fire or explosion via a connected line — injury to persons (S3)
R_V22.4e-05Fire or explosion via a connected line — physical damage (S3)

Recommended protection measures

With the recommended measures every risk zone satisfies R <= R_T (projected governing-zone risk 5.42e-06/yr).

Detailed calculation steps

The derivation chain shared by every risk zone, with the substituted values and the clause each step implements — check any step against the standard.

#StepWorkingResult
1 Lightning ground strike-point density
IEC 62305-2:2024, §A.1, eq. A.1
N_SG = k × N_G
k = 2, N_G = 4 /km²/yr
N_SG = 8 /km²/yr
2 Collection area of the structure
IEC 62305-2:2024, §A.2.1.2, eq. A.3
A_D = L·W + 2·(3H)·(L+W) + π·(3H)²
L = 30 m, W = 20 m, H = 8 m
A_D = 4,809.56 m²
3 Flashes to the structure
IEC 62305-2:2024, §A.2.4, eq. A.5; Table A.1
N_D = N_SG · A_D · C_D · 10⁻⁶
N_SG = 8, A_D = 4,809.56 m², C_D = 1 (isolated)
N_D = 0.0384765 /yr
4 Flashes near the structure
IEC 62305-2:2024, §A.3, eqs. A.7/A.8
r_M = 350/U_W ; A_M = 2·r_M·(L+W) + π·r_M² ; N_M = (1/k)·N_SG·A_M·10⁻⁶
U_W(min) = 1.5 kV → r_M = 233.333 m, L = 30 m, W = 20 m, A_M = 194,376 m², k = 2 (§A.1 NOTE 1 fallback — where N_SG comes from a lightning location system, k is supplied by that provider)
N_M = 0.777502 /yr
5 Flashes to line 'power'
IEC 62305-2:2024, §A.4, eqs. A.9/A.10; Tables A.2–A.4
A_L = 40 · L_L ; N_L = N_SG · A_L · C_I · C_E · C_T · 10⁻⁶
L_L = 200 m → A_L = 8,000 m²; C_I = 0.3, C_E = 0.5, C_T = 1
N_L = 0.0096 /yr
6 Flashes near line 'power'
IEC 62305-2:2024, §A.5, eqs. A.11/A.12
r_I = 2000/U_W^1.8 ; A_I = 2·r_I·L_L ; N_I = (1/k)·N_SG·A_I·C_I·C_E·C_T·10⁻⁶
U_W = 2.5 kV, L_L = 200 m → A_I = 153,744 m²; k = 2
N_I = 0.0922464 /yr
7 Flashes to line 'telecom'
IEC 62305-2:2024, §A.4, eqs. A.9/A.10; Tables A.2–A.4
A_L = 40 · L_L ; N_L = N_SG · A_L · C_I · C_E · C_T · 10⁻⁶
L_L = 500 m → A_L = 20,000 m²; C_I = 1, C_E = 0.5, C_T = 1
N_L = 0.08 /yr
8 Flashes near line 'telecom'
IEC 62305-2:2024, §A.5, eqs. A.11/A.12
r_I = 2000/U_W^1.8 ; A_I = 2·r_I·L_L ; N_I = (1/k)·N_SG·A_I·C_I·C_E·C_T·10⁻⁶
U_W = 1.5 kV, L_L = 500 m → A_I = 963,975 m²; k = 2
N_I = 1.92795 /yr
9 Per-zone risk and verdict
IEC 62305-2:2024, eqs. 6–9, Table 3, §7.3
R = R_L1 + R_L2 ; each R_X = N_X · P_X · L_X (with P_P/P_e per Table 3)
per-zone components and resolved factors in the tables below
protection required unless R ≤ R_T = 1e-05 /yr in every zone

Resolved factors — zone Sales floor

FactorValueDerivation
P_P 0.342466 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.001 Table B.2 (surface of soil or floor)
r_f 0.01 Table B.6, fire load 'ordinary'
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 0.5 Table B.4 (construction material)
P_LPS 1 Table B.3 (class of LPS)
P_AT 0.001 = P_LPS · P_am · r_t · P_TWS (eq. B.2)
P_B 0.0025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 1 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 0.001 = P_am · P_EB · P_LD · P_TWS · C_LD · r_t (eq. B.10)
P_V (power) 0.005 = P_EB · P_LD · P_TWS · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_TWS · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · P_TWS · C_LI (eq. B.13)
C_LD (telecom) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (telecom) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (telecom) 1 Table B.13 (line-entrance bonding SPDs)
P_LD (telecom) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (telecom) 0.001 = P_am · P_EB · P_LD · P_TWS · C_LD · r_t (eq. B.10)
P_V (telecom) 0.005 = P_EB · P_LD · P_TWS · C_LD · r_f · r_p (eq. B.11)
P_W (telecom) 1 = P_SPD · P_TWS · P_LD · C_LD (eq. B.12)
P_Z (telecom) 1 = P_SPD · P_TWS · C_LI (eq. B.13)

Resolved factors — zone Storeroom

FactorValueDerivation
P_P 0.0228311 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.01 Table B.2 (surface of soil or floor)
r_f 0.1 Table B.6, fire load 'high'
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 0.5 Table B.4 (construction material)
P_LPS 1 Table B.3 (class of LPS)
P_AT 0.01 = P_LPS · P_am · r_t · P_TWS (eq. B.2)
P_B 0.025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 1 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 0.01 = P_am · P_EB · P_LD · P_TWS · C_LD · r_t (eq. B.10)
P_V (power) 0.05 = P_EB · P_LD · P_TWS · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_TWS · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · P_TWS · C_LI (eq. B.13)

Projected outcome with the recommended measures

The same assessment re-run with the recommended protection measures applied. The projected figures are reproducible from the post-measure factors below, exactly as the unprotected result is from the tables above.

ZoneProjected RRL1 (injury)RL2 (damage)Tolerable RTVerdict
Sales floor 1.26e-06 3.31e-07 9.29e-07 1e-05 Pass
Storeroom 5.42e-06 1.26e-07 5.29e-06 1e-05 Pass

Resolved factors with measures applied — zone Sales floor

FactorValueDerivation
P_P 0.342466 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.001 Table B.2 (surface of soil or floor)
r_f 0.01 Table B.6, fire load 'ordinary'
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 1 = 1 with an LPS installed (Table B.4 NOTE 1)
P_LPS 0.05 Table B.3 (class of LPS)
P_AT 5e-05 = P_LPS · P_am · r_t · P_TWS (eq. B.2)
P_B 0.00025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 0.02 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 2e-05 = P_am · P_EB · P_LD · P_TWS · C_LD · r_t (eq. B.10)
P_V (power) 0.0001 = P_EB · P_LD · P_TWS · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_TWS · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · P_TWS · C_LI (eq. B.13)
C_LD (telecom) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (telecom) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (telecom) 0.02 Table B.13 (line-entrance bonding SPDs)
P_LD (telecom) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (telecom) 2e-05 = P_am · P_EB · P_LD · P_TWS · C_LD · r_t (eq. B.10)
P_V (telecom) 0.0001 = P_EB · P_LD · P_TWS · C_LD · r_f · r_p (eq. B.11)
P_W (telecom) 1 = P_SPD · P_TWS · P_LD · C_LD (eq. B.12)
P_Z (telecom) 1 = P_SPD · P_TWS · C_LI (eq. B.13)

Resolved factors with measures applied — zone Storeroom

FactorValueDerivation
P_P 0.0228311 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.01 Table B.2 (surface of soil or floor)
r_f 0.1 Table B.6, fire load 'high'
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 1 = 1 with an LPS installed (Table B.4 NOTE 1)
P_LPS 0.05 Table B.3 (class of LPS)
P_AT 0.0005 = P_LPS · P_am · r_t · P_TWS (eq. B.2)
P_B 0.0025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 0.02 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 0.0002 = P_am · P_EB · P_LD · P_TWS · C_LD · r_t (eq. B.10)
P_V (power) 0.001 = P_EB · P_LD · P_TWS · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_TWS · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · P_TWS · C_LI (eq. B.13)
What this assessment does not cover. Stated for every assessment, whether or not it applies to yours: