This is a sample report. It is the complete document you receive when you unlock a report — same template, same engine, on one fixed example building. Your own structure gets its own computation, with your inputs and your figures throughout.
Assess your structure — free → See pricing
Lightning Protection Risk Assessment
per IEC 62305-2:2024
Voltbench v0.1.0
Report VB-SAMPLE-0001
2026-07-01 09:30
StructureRetail block — 3 storeys (sample) Basis of calculationIEC 62305-2:2024
Enginelightning-0.4.0-iec2024 Schemav2
Governing zone risk
7.39e-05
Tolerable
1e-05
Verdict
Exceeds tolerable
Assumptions for missing inputs — the engine filled in the following defaults; verify each before relying on this assessment:
Methodology notes (Ed. 3:2024)

Risk zones

Risk is assessed for each risk zone and compared with the tolerable risk in that zone; protection is required unless every zone complies.

10⁻⁸ 10⁻⁷ 10⁻⁶ 10⁻⁵ 10⁻⁴ R_T Sales floor: R = 3.7e-05 /yr — Exceeds Sales floor 3.7e-05 · Exceeds Storeroom: R = 7.39e-05 /yr — Exceeds Storeroom 7.39e-05 · Exceeds
ZoneRisk RRL1 (injury)RL2 (damage)Tolerable RTVerdict
Sales floor 3.7e-05 9.76e-06 2.72e-05 1e-05 Exceeds
Storeroom 7.39e-05 1.76e-06 7.21e-05 1e-05 Exceeds

Risk component breakdown — governing zone

R_B2 = 4.81e-05 /yr — Fire or explosion — physical damage (S1) R_B2 4.81e-05 R_V2 = 2.4e-05 /yr — Fire or explosion via a connected line — physical damage (S3) R_V2 2.4e-05 R_B1 = 1.1e-06 /yr — Fire or explosion — injury to persons (S1) R_B1 1.1e-06 R_V1 = 5.48e-07 /yr — Fire or explosion via a connected line — injury to persons (S3) R_V1 5.48e-07 R_AT = 8.78e-08 /yr — Touch and step voltages — flash to the structure (S1) R_AT 8.78e-08 R_U = 2.19e-08 /yr — Touch voltage via a connected line — injury to persons (S3) R_U 2.19e-08
ComponentValueDescription
R_AT8.78e-08Touch and step voltages — flash to the structure (S1)
R_B11.1e-06Fire or explosion — injury to persons (S1)
R_B24.81e-05Fire or explosion — physical damage (S1)
R_U2.19e-08Touch voltage via a connected line — injury to persons (S3)
R_V15.48e-07Fire or explosion via a connected line — injury to persons (S3)
R_V22.4e-05Fire or explosion via a connected line — physical damage (S3)

Recommended protection measures

With the recommended measures every risk zone satisfies R <= R_T (projected governing-zone risk 5.42e-06/yr).

Detailed calculation steps

The derivation chain shared by every risk zone, with the substituted values and the clause each step implements — check any step against the standard.

#StepWorkingResult
1 Lightning ground strike-point density
IEC 62305-2:2024, §A.1, eq. A.1
N_SG = k × N_G
k = 2, N_G = 4 /km²/yr
N_SG = 8 /km²/yr
2 Collection area of the structure
IEC 62305-2:2024, §A.2.1.2, eq. A.3
A_D = L·W + 2·(3H)·(L+W) + π·(3H)²
L = 30 m, W = 20 m, H = 8 m
A_D = 4,809.56 m²
3 Flashes to the structure
IEC 62305-2:2024, §A.2.4, eq. A.5; Table A.1
N_D = N_SG · A_D · C_D · 10⁻⁶
N_SG = 8, A_D = 4,809.56 m², C_D = 1 (isolated)
N_D = 0.0384765 /yr
4 Flashes near the structure
IEC 62305-2:2024, §A.3, eqs. A.7/A.8
r_M = 350/U_W ; A_M = 2·r_M·(L+W) + π·r_M² ; N_M = (1/k)·N_SG·A_M·10⁻⁶
U_W(min) = 1.5 kV → r_M = 233.333 m, A_M = 194,376 m², k = 2
N_M = 0.777502 /yr
5 Flashes to line 'power'
IEC 62305-2:2024, §A.4, eqs. A.9/A.10; Tables A.2–A.4
A_L = 40 · L_L ; N_L = N_SG · A_L · C_I · C_E · C_T · 10⁻⁶
L_L = 200 m → A_L = 8,000 m²; C_I = 0.3, C_E = 0.5, C_T = 1
N_L = 0.0096 /yr
6 Flashes near line 'power'
IEC 62305-2:2024, §A.5, eqs. A.11/A.12
r_I = 2000/U_W^1.8 ; A_I = 2·r_I·L_L ; N_I = (1/k)·N_SG·A_I·C_I·C_E·C_T·10⁻⁶
U_W = 2.5 kV, L_L = 200 m → A_I = 153,744 m²; k = 2
N_I = 0.0922464 /yr
7 Flashes to line 'telecom'
IEC 62305-2:2024, §A.4, eqs. A.9/A.10; Tables A.2–A.4
A_L = 40 · L_L ; N_L = N_SG · A_L · C_I · C_E · C_T · 10⁻⁶
L_L = 500 m → A_L = 20,000 m²; C_I = 1, C_E = 0.5, C_T = 1
N_L = 0.08 /yr
8 Flashes near line 'telecom'
IEC 62305-2:2024, §A.5, eqs. A.11/A.12
r_I = 2000/U_W^1.8 ; A_I = 2·r_I·L_L ; N_I = (1/k)·N_SG·A_I·C_I·C_E·C_T·10⁻⁶
U_W = 1.5 kV, L_L = 500 m → A_I = 963,975 m²; k = 2
N_I = 1.92795 /yr
9 Per-zone risk and verdict
IEC 62305-2:2024, eqs. 6–9, Table 3, §7.3
R = R_L1 + R_L2 ; each R_X = N_X · P_X · L_X (with P_P/P_e per Table 3)
per-zone components and resolved factors in the tables below
protection required unless R ≤ R_T = 1e-05 /yr in every zone

Resolved factors — zone Sales floor

FactorValueDerivation
P_P 0.342466 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.001 Table B.2 (surface of soil or floor)
r_f 0.01 Table B.6 (fire/explosion risk)
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 0.5 Table B.4 (construction material)
P_LPS 1 Table B.3 (class of LPS)
P_AT 0.001 = P_LPS · P_am · r_t (eq. B.2)
P_B 0.0025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 1 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 0.001 = P_am · P_EB · P_LD · C_LD · r_t (eq. B.10)
P_V (power) 0.005 = P_EB · P_LD · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · C_LI (eq. B.13)
C_LD (telecom) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (telecom) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (telecom) 1 Table B.13 (line-entrance bonding SPDs)
P_LD (telecom) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (telecom) 0.001 = P_am · P_EB · P_LD · C_LD · r_t (eq. B.10)
P_V (telecom) 0.005 = P_EB · P_LD · C_LD · r_f · r_p (eq. B.11)
P_W (telecom) 1 = P_SPD · P_LD · C_LD (eq. B.12)
P_Z (telecom) 1 = P_SPD · C_LI (eq. B.13)

Resolved factors — zone Storeroom

FactorValueDerivation
P_P 0.0228311 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.01 Table B.2 (surface of soil or floor)
r_f 0.1 Table B.6 (fire/explosion risk)
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 0.5 Table B.4 (construction material)
P_LPS 1 Table B.3 (class of LPS)
P_AT 0.01 = P_LPS · P_am · r_t (eq. B.2)
P_B 0.025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 1 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 0.01 = P_am · P_EB · P_LD · C_LD · r_t (eq. B.10)
P_V (power) 0.05 = P_EB · P_LD · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · C_LI (eq. B.13)

Projected outcome with the recommended measures

The same assessment re-run with the recommended protection measures applied. The projected figures are reproducible from the post-measure factors below, exactly as the unprotected result is from the tables above.

ZoneProjected RRL1 (injury)RL2 (damage)Tolerable RTVerdict
Sales floor 1.26e-06 3.31e-07 9.29e-07 1e-05 Pass
Storeroom 5.42e-06 1.26e-07 5.29e-06 1e-05 Pass

Resolved factors with measures applied — zone Sales floor

FactorValueDerivation
P_P 0.342466 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.001 Table B.2 (surface of soil or floor)
r_f 0.01 Table B.6 (fire/explosion risk)
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 1 = 1 with an LPS installed (Table B.4 NOTE 1)
P_LPS 0.05 Table B.3 (class of LPS)
P_AT 5e-05 = P_LPS · P_am · r_t (eq. B.2)
P_B 0.00025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 0.02 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 2e-05 = P_am · P_EB · P_LD · C_LD · r_t (eq. B.10)
P_V (power) 0.0001 = P_EB · P_LD · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · C_LI (eq. B.13)
C_LD (telecom) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (telecom) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (telecom) 0.02 Table B.13 (line-entrance bonding SPDs)
P_LD (telecom) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (telecom) 2e-05 = P_am · P_EB · P_LD · C_LD · r_t (eq. B.10)
P_V (telecom) 0.0001 = P_EB · P_LD · C_LD · r_f · r_p (eq. B.11)
P_W (telecom) 1 = P_SPD · P_LD · C_LD (eq. B.12)
P_Z (telecom) 1 = P_SPD · C_LI (eq. B.13)

Resolved factors with measures applied — zone Storeroom

FactorValueDerivation
P_P 0.0228311 = t_z / 8760 (eq. B.14)
P_e 1 = 1 — time of exposure unknown (§B.12 NOTE 1)
P_am 1 Table B.1 (touch/step-voltage measures)
r_t 0.01 Table B.2 (surface of soil or floor)
r_f 0.1 Table B.6 (fire/explosion risk)
r_p 0.5 Table B.5 (fire-reducing provisions)
P_S 1 = 1 with an LPS installed (Table B.4 NOTE 1)
P_LPS 0.05 Table B.3 (class of LPS)
P_AT 0.0005 = P_LPS · P_am · r_t (eq. B.2)
P_B 0.0025 = P_S · P_LPS · r_f · r_p (eq. B.4)
L_T 0.01 Table C.2 typical value
L_F1 0.05 Table C.2 typical value
L_F2 0.05 Table C.2 typical value
K_S2 1 zone shielding screen (§B.6, eq. B.9)
P_C 1 = 1 − Π(1 − P_SPD·C_LD) over internal systems (eq. 10; eq. B.5)
P_M 1 = 1 − Π(1 − P_SPD·(K_S1·K_S2·K_S3)²) (eq. 11; eqs. B.6/B.7)
C_LD (power) 1 Table B.9 (line shielding/grounding/isolation)
C_LI (power) 1 Table B.9 (line shielding/grounding/isolation)
P_EB (power) 0.02 Table B.13 (line-entrance bonding SPDs)
P_LD (power) 1 Tables B.11/B.12 (line shielding vs U_W)
P_U (power) 0.0002 = P_am · P_EB · P_LD · C_LD · r_t (eq. B.10)
P_V (power) 0.001 = P_EB · P_LD · C_LD · r_f · r_p (eq. B.11)
P_W (power) 1 = P_SPD · P_LD · C_LD (eq. B.12)
P_Z (power) 1 = P_SPD · C_LI (eq. B.13)