External LPS Design
Commercial block — 5 storeys (sample)
Report VB-LPS-SAMPLE-0001 · v1
Generated 2026-07-01 09:30
Engine lps-1.4.0-iec2024 · schema v1

Basis of calculation: IEC 62305-3:2024 (Ed. 3.0)

Air termination

LPS classII
MethodMesh
Maximum mesh size10 m × 10 m

Mesh conductors on the roof perimeter and ridges; no metal installation outside the protected volume.

One dimension of a mesh cell may be increased by up to +25 % provided the cell perimeter is not increased (Table 2 provision).

Down conductors

Perimeter128 m
Typical spacing10 m
Required down conductors13

Fit a test joint on each of the 13 down conductors at its connection to the earth termination, openable for measurement (§5.3.6).

Separation distance

k_i (class)0.06
k_c (current division)0.44 — 13 down conductor(s)
k_m (material)1 — Air
Length l20 m
Point considered20 m above ground
Per-level k_clevel 1: 0.337, level 2: 0.177
Required separation s (general)0.309 m
Simplified comparison0.528 m (general saves 42 %)

General approach assumes all down conductors interconnected by ring conductors at the stated spacing (§5.3.4, Figure B.3).

The segment sum runs to the earth termination (bonding at ground level only — conservative). Where the internal installation is bonded at a ring level, only the segments above that level apply (Figure B.3, cases a–e).

Every internal metal installation closer than s to a down conductor must be bonded or the distance increased.

For an LPS installed at high elevations an altitude correction applies (§6.3.2, per IEC 60071-2).

Earth termination

ArrangementType B (ring electrode)
Soil resistivity ρ1500 Ω·m
Minimum length l_119.0 m
Ring requirementmean radius of enclosed area r_e ≥ 19.0 m
Effective ring radius r_e18.6 m (from footprint, ring ≈ 1 m out)
Ring criterionnot met — additional electrodes required
Additional electrodes13 × horizontal ≥ 0.4 m, or vertical ≥ 0.2 m

The minimum lengths may be disregarded where the earth-termination resistance achieved is below 10 Ω (measured at low frequency).

Ring in contact with the soil for at least 80 % of its length, buried ≥ 0,5 m deep, about 1 m from the external walls (§5.4.3).

Connect the additional electrodes to the ring where the down conductors connect, as equidistantly as possible.

Materials & minimum dimensions

LPS conductor materialCopper / tin-plated copper
Solid tape, minimum50 mm²
Solid round, minimum50 mm²
Stranded, minimum50 mm²
Air-termination rods176 mm² solid round
Earth-electrode materialCopper / tin-plated copper
Earth rod (solid round)Ø 15 mm
Earth rod (tubular)Ø 20 mm
Buried earth conductor50 mm²
Earth plate500 × 500 mm

All LPS components (conductors, rods, electrodes, clamps) shall meet IEC 62561-2 mechanical/electrical/corrosion requirements (Table 7/8 note a).

Air-termination rods where mechanical stress such as wind loading is not critical may be reduced to 9,5 mm diameter, 1 m long (Table 7 note c).

Copper solid round 50 mm² (8 mm Ø) may be reduced to 28 mm² (6 mm Ø) where mechanical strength is not essential; reduce fastener spacing accordingly (Table 7 note b).

A buried copper earth electrode shall not be used in contact with the structure's steel members, pipes or piles — corrosion (Table 8 note g).

Equipotential bonding (internal LPS)

Bonding conductor materialCopper
Bars ↔ bars / bar ↔ earth termination16 mm² (Table 9)
Internal installations ↔ bonding bar6 mm² (Table 10)

Install the main bonding bar in the basement or at ground level, accessible for inspection, and connect it to the earth-termination system (§6.2.2 a).

Structure length 40 m exceeds 20 m — use a ring bonding bar or several interconnected bonding bars (§6.2.2 a).

Bond additionally at every point where the separation distance s of the section above cannot be kept (§6.2.2 b). Keep bonding connections as direct and straight as possible.

Live conductors of internal systems are bonded via SPDs — coordinate per IEC 62305-4.

Touch & step voltages

People within 3 m of down conductorsyes (assumed)
AssessmentProtection measures required
Touch-voltage measuresInsulate exposed down conductors to 100 kV, 1,2/50 µs impulse withstand (e.g. ≥ 3 mm cross-linked polyethylene), or apply physical restrictions / warning notices
Step-voltage measuresEquipotentialize with a meshed earth-termination system, or apply physical restrictions / warning notices within 3 m of the down conductors

The insulation withstand voltage should be considered in wet conditions (§8.1). Signage shall conform to ISO 3864-1.

Alternative exemption (§8.1 c / §8.2 c): a measured contact resistance of the soil surface layer within 3 m of the down conductors of at least 100 kΩ (over a 0,02 m² footprint) also brings the hazard to a tolerable level — a 5 cm layer of insulating material, e.g. asphalt, generally achieves this.

Inspection & maintenance

Site environmentSensitive internal systems / high occupancy
Visual inspectionevery year
Complete inspection (incl. electrical testing)every year

Also inspect: during construction (components that become concealed), after LPS installation, after alterations or repairs, and after a known or suspected lightning strike to the structure (§7.4).

Periodic checks: deterioration and corrosion of air-termination elements, conductors and connections; earthing resistance of the earth-termination system; condition of connections, equipotential bonding and fixings (§7.4).

Testing on a 14–15-month cycle is acceptable where earth-resistance readings across different seasons are wanted (D.7.2.2). Consider improving the earthing system when measured resistance rises over successive inspections.

Record all inspection and test results and keep them with the LPS design documentation for the property manager (§7.4).

Assumptions for missing inputs

Calculation trace

StepFormulaValuesResultReference
Mesh size w_m = w_m(class) class II 10 m × 10 m IEC 62305-3:2024 §5.2.2 (values: Ed. 2 Table 2)
Down-conductor count n = max(2, ⌈perimeter / spacing⌉) perimeter = 128 m, spacing = 10 m (class II) n = 13 IEC 62305-3:2024 §5.3.3 (values: Ed. 2 Table 4)
Separation distance (simplified) s = k_i · k_c · l / k_m k_i = 0.06, k_c = 0.44, l = 20 m, k_m = 1 s = 0.528 m IEC 62305-3:2024 §6.3.2, eq. (6), Table 13
k_c per level (ring-interconnected down conductors) k_c1 = 1/(2n) + 0.1 + 0.2·∛(c/h₁); k_c2 = 1/n + 0.1; k_c3 = 1/n + 0.01; k_c4… = 1/n n = 13, c = 9.8 m k_c1 = 0.337, k_c2 = 0.177 IEC 62305-3:2024 Annex B, Figure B.3
Separation distance (general approach) s = k_i/k_m · Σ (k_cn · l_n) k_i = 0.06, k_m = 1; Σ = 0.337·10 + 0.177·10 s = 0.309 m IEC 62305-3:2024 §6.3.1, eq. (5); Annex B
Minimum electrode length l_1 = l_1(class, ρ) class II, ρ = 1500 Ω·m l_1 = 19.0 m IEC 62305-3:2024 §5.4.2, Figure 5
Type B ring criterion r_e ≥ l_1 l_1 = 19.0 m r_e ≥ 19.0 m IEC 62305-3:2024 §5.4.2.3, eq. (1)
Effective ring radius r_e = √(A/π), A = (L+2)·(W+2) L = 40 m, W = 24 m r_e = 18.6 m IEC 62305-3:2024 §5.4.2.3 (r_e of the enclosed area)
Type B additional electrodes l_r = l_1 − r_e ; l_v = (l_1 − r_e) / 2 l_1 = 19.0 m, r_e = 18.6 m l_r ≥ 0.4 m or l_v ≥ 0.2 m, × 13 IEC 62305-3:2024 §5.4.2.3, eq. (2)/(3)

Installation notes