Calculator · IEC 62305-3 · Ed. 3.0:2024

Separation distance calculator, IEC 62305-3

The simplified method of §6.3.2: one current-division coefficient over the whole length. Enter five inputs. The answer comes with every coefficient, the table it is read from, and the formula with your numbers in it.

Inputs

A published worked example, shown until you calculate your own: LPS Class IV, concrete walls, Type A earthing in the dissimilar-resistance case, at the roof edge (l = 15 m). The source gives 1.2 m. How it reconciles →

Required separation distance

s = 1.200 m

s = ki · kc · l / km
  = 0.04 × 1 × 15 m / 0.5
  = 1.200 m

ki0.04LPS class (Table 11).
kc1Type A earthing whose neighbouring electrode resistances are not shown to be within a factor of 2 of each other: k_c = 1 (Table 13, note).
km0.5What fills the gap (Table 12).
l15 mAs entered.

IEC 62305-3:2024 §6.3.2, eq. (6); Tables 11, 12 and 13.

Every internal metal installation closer than s to the conductor must be bonded to it, or the distance increased.

This separation distance is not altitude-corrected. §6.3.2 requires a correction for an LPS installed at high elevations, following IEC 60071-2. Site elevation is not an input here and no correction has been applied, so where the site is at elevation, read §6.3.2 against it and adjust s accordingly.